Safehouse Quiet Reset Smoke Alarm (490-0458) NFPA Recommendations Faxback Doc. # 34308 NFPA RECOMMENDATIONS For your information, the National Fire Protection Association's Standard 74, Chapter 2, reads as follows: 2-1.1 This standard requires the following detectors within the family unit. 2-1.1.1 Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each additional story of the family living unit including the basement and excluding crawl spaces and unfinished attics. (See note 1, below.) NOTE 1 - The provisions of 2-1.1.1 represent the minimum number of detectors required by this standard. It is recommended that the householders consider the use of additional smoke or heat detectors for increased protection of areas separated by a door from the areas protected by the required smoke detectors under 2-1.1.1 above. The recommended additional areas are: living room, dining room, bedroom(s), kitchen, attic (finished or unfinished), furnace room, utility room, basement, integral or attached garage, and hallways not covered under 2-1.1.1 above. However, the use of additional detectors remains the option of the householder. 2-1.1.2 For family living units with one or more split levels (i.e., adjacent levels with less than one full story separation between levels), a smoke detector required by 2-1.1.1 shall suffice for an adjacent lower level, including basements. Exception: Where there is an intervening door between one level and the adjacent lower level, a smoke detector shall be installed on the lower level. 2-2 Alarm Sounding Devices. Each detection device shall cause the operation of an alarm which shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed. The tests of audibility level shall be conducted with all household equipment which may be in operation at night in full operation. Examples of such equipment are window air conditions and room humidifiers. (LB/EB 08/01/96)